107-CNC-FDDP zoom
107-CNC-FDDP

FireChase CNC Detection and Actuation System

$950.00 AUD; GST Excl.

Bulk Pricing:
5 - 9 (5% off) 10 - 14 (10% off) 15 - 19 (15% off) 20 + (20% off)
$902.50 $855.00 $807.50 $760.00
SKU: 107 CNC-FDDP Categories: ,

This panels unique industrial design is suitable for fire detection and activation of fire suppression systems and PLC controllers used in CNC machines.
It provides a communication interface between PLC of CNC machine and FireChase Panel. The panel is built with features of an industrial fire system including fault monitoring of internal and external circuits. The communication interface provides PLC and CNC operator notifications regarding fire system conditions.
          Application
CNC machines
          Fire Suppressants
Any commercial fire suppressant can be used with the panel.
          Requirements for Fire-Fighting in CNC Machines
In order to avoid damage to the machine from potential fires, the system must extinguish the fire within 5-7 seconds.
A fire under a closed machine canopy is fuelled by a continuous flow of:
–  Flammable coolant oil sprayed under high pressure
–  Air from the exhaust ventilation of the machine

Extinguishing the flame inside the machine imposes very specific requirements on the fire detection and extinguishing system:
– Quick detection response to fire (1-2 seconds)
– Discharge the extinguishing system without a standard delay
– Very quick discharge of the extinguishing agent (5-7 seconds)
– Coordination of the actions of the extinguishing system and the operation of the machine
– Immediate disconnection of the power supply to the machine using the fire protection system
– Autonomous operation of the fire system after disconnecting the power supply
– Replacement of the system within a few hours after extinguishing a fire to minimize losses from machine downtime

Fire from one ignited machine can easily spread to other machines on the production line through the general ventilation system.

      

Operating Voltage

12-24V DC

Current

Panel Normal Current on External Power Supply: 100mA
Panel Normal Current on Internal Power Supply: 40mA

Suppressant Module Monitoring Current: 1mA
Suppressant Module Discharge Current: 1.0A

Power Supply

External Power Supply: 24VDC, 1.5A Capable
Internal Standby Battery: 12V, 1.3AH

Time Duration for Battery Support

5-6 minutes (after external power is switched off)

Battery Float Charge Voltage

13.75V

Battery Charger Current Limit

0.8A

Dimensions

Fascia: 180mm (width), 130mm (height), 3mm (depth)
Box: 153mm (width), 103mm (height), 83mm (depth)

Monitor Contact Outputs

– E-Stop, normally closed, 2 off
– Fire System Ready, normally closed, fail-safe
– Fire System Fault, normally closed
– Panel Alarm, change-over

Resistors

Temperature Probe End-Of-Line Resistor: 8K2 Ω, ¼W
External Breakglass End-Of-Line Resistor: 8K2 Ω, ¼W

Manuals

Click here for the manual: FireChase CNC Detection and Actuation System Manual (107)