303 zoom
303

T-Start 72°C (Automatic Detection and Activation)

$190.00 AUD; GST Excl.

Click here to visit the T-Start Shop Page.

Model T(72°)-Start (Standard Application)
Model T(110°)-Start (Suitable for Motor Rooms and Tracks)
Model T(M)-Start (Designed for Manual Activation)

Protective Cup – For usage in harsh environments
Detection Circuit Junction Box –  Allows for the connection of the T-Start device to an existing Fire Detection Line
Protective Casing for External Mounting (Only for Manual T-Start)

Bulk Pricing:
5 - 9 (5% off) 10 - 14 (10% off) 15 - 19 (15% off) 20 + (20% off)
$180.50 $171.00 $161.50 $152.00
SKU: 303-T-72 Category:

Description
The T-Start 72°C is an autonomous and automatic thermal detection and activation device, that allows for the detection of a fire and the activation of a powder, aerosol or gaseous fire suppression system. The T-Start can be used as a thermal detector with a fixed temperature reading (72ºC).

The T-Start can be partnered with the specially designed ‘Detection Circuit Junction Box’, which provides a signal to a fire panel, and an additional output to shut down electrical equipment, or to activate alarms (depending on modifications).
The T-Start can also be partnered with a specially designed ‘Protective Cup’, which allows the T-Start to operate in more harsh environments (dust, splash, etc.). However, note that the ‘Protective Cup’ will reduce the sensitivity of the heat-sensitive element, and as a result, the activation time increases.

Design
The T-Start device is designed for the autonomous and automatic activation of a fire suppression system. No external power supply is required.

Rated Activation Temperature

+72ºC ±5ºC

Operation Temperature Ranges

-60 to +55 ºC

Area Dimensions

The dimensions of a protected area shall not exceed 18m³:
Height – 3.0 meters
Width – 2.4 meters
Length – 2.5 meters

One electric circuit can support 10 T-Start devices, increasing the protected area up to 180m³.

Output

The device generates an electric impulse with the amplitude of 3.5V DC at a circuit resistance
of 1.0 Ohm. The device can activate the following types of electrical initiators: MB-2H, 3A-1, PP-9, YGP-10, and
similar.

Relative Humidity

The maximum relative humidity is – 98% (no condensation)

Mass and Dimensions

Length: < 85mm
Diameter: < 65mm
Total Mass: < 0.2kg
(excluing Protective Cup and Junction Box)

Service Life

The reliability of the device is not less than 50,000 hours under normal ambient conditions. The service life of the device is 10 years.

SCHEMATICS & MORE INFORMATION:

Please view the manual (located in the 'Manual' tab) for more information, and T-Start diagrams.

Manuals

Click here for the T-Start and T-Start Accessories Manual: T-Start Manual